HFC227ea UNITS (FM200)

 

Volume Calculation

 Maintenance & Servicing

bullet All units supplied with a sprinkler bulb operative at a temperature of 79°C as standard.
bullet Modular HFC-227ea units can be supplied in sizes from 1.0 to 21kg.
bullet Normally automatically operated Roof Mounted but also available with mechanical or electrical *override.
bullet Pressure gauge fitted as standard on all units.
bullet Pressure switch available on request.
bullet Relative light weight allows bulk
head mounting.
bullet Light weight makes installation, handling and servicing easy.
bullet Cylinders can be located in fire
risk areas.
bullet 'Inverted' units fit vertically with discharge at bottom of unit.
bullet 'Roof Mounted' units can be fitted vertically (discharge at top) or horizontally.

 

Cylinder qty
(kg)
Unit Size
mm
Area
Protected
(m³)
Cylinder type
*1.0 320 x 80 1.34 Alum
*1.5 370 x 108 2.00 Alum
*2.0 370 x 108 2.67 Alum
       
1.0 199 x 140 1.34 Steel
1.5 292 x 124 2.00 Steel
2.0 292 x 124 2.67 Steel
2.5 292 x 124 3.34 Steel
3.0 420 x 170 4.00 Steel
3.5 420 x 170 4.67 Steel
4.0 420 x 170 5.34 Steel
4.5 420 x 170 6.00 Steel
5.0 420 x 170 6.67 Steel
5.5 420 x 170 7.34 Steel
6.0 420 x 170 8.00 Steel
6.5 420 x 170 8.67 Steel
7.0 432 x 254 9.34 Steel
8.0 432 x 254 10.67 Steel
9.0 432 x 254 12.00 Steel
10.0 432 x 254 13.34 Steel
11.0 432 x 254 14.67 Steel
12.0 710 x 225 16.00 Steel
13.0 710 x 225 17.34 Steel
14.0 710 x 225 18.67 Steel
15.0 710 x 225 20.00 Steel
16.0 710 x 225 21.34 Steel
17.0 710 x 225 22.67 Steel
18.0 710 x 225 24.00 Steel
19.0 710 x 225 25.34 Steel
20.0 710 x 225 26.67 Steel
21.0 710 x 225 28.00 Steel

   * Cannot be fitted with mechanical or electronic overrides

 

 

Buy Flamecheater Automatic Marine Fire Protection Systems.

Volume Calculation

To calculate the volume of your engine compartment:
Measure length (L), Width (W) & Height (H) of compartment in metres.

Volume = L x W x H

It is permissible to take off any areas such as tanks that are totally sealed within the space, but the volume of the engine should not be taken off, as if the engine is running when the system operates, it will draw in a percentage of extinguishant before stopping.

Back

 

 

 

Auto / Mechanical Units

All units supplied with a 2m long  operating cable, pull handle and protective bracket, and a sprinkler bulb operative at a temperature of 79° C (175° F) as standard. Other ratings available on request.

Back

 

 

 

Auto / Electrical Units

All units supplied with latching plug in lead, 2m long. Power source required to operate each unit is 1 amp for 10 milliseconds. Sprinkler bulb operative at a temperature of 79° C (175° F) as standard. Other ratings available on request.

Back

 

 
 

 

 

Auto Roof Units

All units supplied with sprinkler bulb operative at a temperature of 79° C (175° F) as standard. Other ratings available on request.

Back

 

 

 

 

Maintenance & Servicing

Manufacturer's recommended maintenance checks and servicing procedures as follows:

Daily/Weekly - Check Gauge Pressure

Six monthly - Check Weight

10 Yearly - Hydrostatic Test by Manufacturer

 

Back

 