Automatic Fire Suppression Units

MP-2-0000 Novec 1230 Range

bullet Clean Agent "Drop In" Halon Replacement.
bullet Low Global Warming Potential.
bullet Manufactured under BS EN ISO 9002
Quality Management.
bullet Stored Pressure - easy low cost maintenance.
bullet Suitable for B & C Fire Classifications.
bullet CE Marked - conforms with Pressure Equipment
Regulations 1999 (SI 1999 No. 2001) &
European PED 97/23/EC.
bullet Zero Ozone Depletion.
bullet Low Atmosphere life (0.014 years).
bullet 1 Year Warranty - Manufactured in the UK.
bullet Safe for use on electrical equipment.
bullet Approved for use in Boat Engine Rooms.

The MP-2 range of Automatic Fire Suppression Units are filled with NOVEC 1230 & pressurised with Nitrogen to 12bar at 20°C. In the event of a fire condition, the unites are designed to operate automatically at a temperature of 68°C +/- 5°C, otherwise the maximum storage/installation temperature is 60°C. The units are fitted with a pressure gauge, pressure switch and pressure relief device. Optional Electrical and or Mechanical release devices are available. Now approved for use in Boat Engine Rooms.

 

Technical Specification
Extinguisher
Model
Capacity Maximum Nett
Volume Protection
Overall Height Overall
Diameter
  KG cu.m. cu.ft mm mm
MP-2-2500 2.5 2.8 98 370 140
MP-2-3000 3.0 3.3 116 370 140
MP-2-3500 3.5 3.9 137 370 140
MP-2-4000 4.0 4.5 158 370 140
MP-2-4500 4.5 5.0 176 370 140
MP-2-5000 5.0 5.6 197 440 170
MP-2-5500 5.5 6.1 215 440 170
MP-2-6000 6.0 6.7 236 440 170
MP-2-6500 6.5 7.3 258 440 170
MP-2-7000 7.0 7.8 275 440 170
MP-2-7500 7.5 8.4 296 440 170
MP-2-8000 8.0 9.0 317 440 170
MP-2-8500 8.5 9.5 335 440 170
MP-2-9000 9.0 10.1 356 440 170
MP-2-9500 9.5 10.6 374 635 175
MP-2-10000 10.0 11.2 395 635 175
MP-2-10500 10.5 11.8 416 635 175
MP-2-11000 11.0 12.3 434 635 175
MP-2-11500 11.5 12.9 455 635 175
MP-2-12000 12.0 13.5 476 635 175
MP-2-12500 12.5 14.0 494 635 175
MP-2-13000 13.0 14.6 515 635 175
MP-2-13500 13.5 15.2 536 635 175
MP-2-14000 14.0 15.7 554 635 175
MP-2-14500 14.5 16.3 575 635 175
MP-2-15000 15.0 16.8 593 635 175

Extinguishant - Novec 1230 - dodecafluror-2-methylpentan-3-one,
{CF3CF2C(0)CF(CF3)2}

Working pressure: 12 bar @ 20°C
* Base on a nominal 6% design concentration

Discharge tine: 10 seconds
(nominal)

Cyl Test Pressure: 26 bar.

 

Important: Maximum volume protected relates to Nett volume, and this MUST NOT be exceeded. Do Not use more that ONE MP-2-0000 Automatic Fire Extinguisher in the volume to be protected.

If you were to use two or more smaller capacity extinguishers for the same volume, there is no guarantee that all would operate at the same time, and as a result may not give the required extinguishant concentration level to extinguish the fire.

Novec™ 1230 Fire Protection Fluid, dodecafluoro-2-methylpentan-3-one, {CF3CF2C(0)CF(CF3)2}, is a clear, colourless and low odour fluid designed as replacements for ozone depleting substances (ODSs) and compounds with high global warming potentials (GWPs) such as HFCs and PFS. Novec 1230 fluid is an effective fire extinguishing agent in standard fire scenarios where halons historically have been used and where halon alternatives are now being used.

Application: Nett Volume = Gross Volume less large permanently fixed structures, namely engine blocks, fuel tanks and water tanks. All other equipment should be classified as being part of the Gross Volume.

MFS Fire Home
Extinguisher Info
Sign Sizes
Contact MFS
Quick Find
SecurityBuy Online

We Accept the Following Cards

Credit Cards